The battery bank load tester structure can provide constant current, constant efficiency, or self-defined discharge process; it automatically stores current, voltage, capacity, and time, and has an RS-232 communication interface, a network-controlled RS-485 interface, and corresponding monitoring software.
|
Product Model |
HDKY-XF48150 |
HDKY-XF48300 |
HDKY-XF22060 |
HDKY-XF60060 |
HDKY-XF600100 |
|
Group Terminal Voltage |
18-60V |
18-60V |
170-270V |
190-600V |
190-600V |
|
Discharge Current (Continuously Adjustable) |
0-150A |
0-300A |
110V:0-30A 220V:0-60A |
0-60A |
0-100A |
|
Control Accuracy |
Discharge current ≤±0.5%; group terminal voltage ≤±0.5%; single cell voltage: ≤±0.3% |
||||
|
Weight |
11kg |
18kg |
18kg |
23kg |
38kg |