Single-Phase-880 Relay Protection Calibration Instrument Equipment Direct Sales in StockSingle-Phase-880 Relay Protection Calibration Instrument Equipment Direct Sales in Stock
Panel Description:
1. ACA (100A, 20A) Output Terminals
2. DCA (5A, 200mA) Output Terminals, Red is "+", Black is "-"
3. ACV Output Terminals
4. DCV Output Terminals, Red is "+", Black is "-"
5. Non-Energized Contact Terminal
6. LCD Display
7. Printer
8. DCA200mA, DCA5A Current Adjustment, Rotate the Knob Clockwise, Current Increases from Small to Large
9. Adjust AC Current, AC Voltage, DC Voltage Knob, Rotate Clockwise, Output Increases from Small to Large
Main Technical Specifications
AC Voltage Output: 0~250V Continuously Adjustable, Maximum Output Current 3A
AC Current Output: 0~20A, 0~100A Continuously Adjustable
At 0~20A, Open Circuit Voltage 2V
At 0~100A, Open Circuit Voltage 10V
DC Voltage Output: 0~300V Continuously Adjustable, Maximum 3A
DC Current Output: 0~200mA, 0~5A Continuously Adjustable
At 0~200 mA, Open Circuit Voltage 15V
At 0~5A, Open Circuit Voltage 15V
Digital Millisecond Meter: Maximum Range: 100 Seconds
Resolution: 0.001 Seconds
Accuracy: 0.01% + 2 Digits
Overall Measurement Accuracy: 0.5 Level
Dimensions: 420ⅹ310ⅹ160
Introduction
Adopting a designed heat dissipation structure to ensure good ventilation. It can simultaneously judge overcurrent, overvoltage, overload, short circuit, excessive temperature, data anomalies, and other phenomena that endanger the safety of the device itself. Even operational errors will not damage the device. In addition, when dangerous signals such as external voltage enter the tester through terminals, the device's alarm indicator light turns red and automatically cuts off the power amplifier.