Direct-reading Salt Density Tester
The Direct-reading Salt Density Tester is used for anti-pollution flashover detection in power systems. It is a measuring instrument for the equivalent salt deposit density (ESDD) on the surface of insulators, and can also measure the conductivity and temperature of the solution. With its high measurement accuracy, wide measurement range, and ease of use, the instrument is widely applied in electric power, education, scientific research, and other related industries.
The classification of pollution levels and the drawing of pollution level distribution maps are the foundation of anti-pollution flashover work. An accurate pollution level distribution map is the basis for selecting the external insulation creepage distance of porcelain insulators for transmission and transformation equipment. The equivalent salt deposit density value on the insulator surface is quantitative data for judging the severity of external insulation pollution, and it is the basis for classifying pollution levels and drawing pollution area maps. Therefore, salt density measurement is of great significance to the safe operation of power systems.
Reference standards:
GB/T16434–1996 "Environmental Pollution Classification and External Insulation Selection for High-Voltage Overhead Lines and Power Plants, Substations"
GB/T16434-200X "Selection and Dimensioning of High-Voltage Insulators for Polluted Conditions - Part 1: Definitions, Information and General Principles"
Q/GDW152-2006 "Environmental Pollution Area Classification and External Insulation Selection for High-Voltage Overhead Lines and Power Plants, Substations"
Functional Features
1) It has an automatic range switching function and fast measurement speed (2.5s/time).
2) Wide measurement range: salt density range 0.0001mg/cm2 to 9.9999mg/cm2.
3) Chinese and English interfaces can be switched independently.
4) Uses a 480*280 color touch LCD screen.
5) Can directly display and print salt density, conductivity, temperature, pollution level, and unified specific creepage distance.
6) Automatically performs temperature compensation, directly displaying the standard conductivity at 20°C and the equivalent salt deposit density (ESDD).
7) Has the function of automatically removing the salt content of the original solution, reducing the requirements for the cleaning solution.
8) Automatically converts the salt density (ESDD) measured without power to the salt density (ESDD) measured with power.
9) Can store 100,000 sets of records, and can export records to a USB drive or print them via a printer.
10) Can view, delete, and export individual records, and can also delete all records.
11) Built-in large-capacity rechargeable lithium battery (2600mAh), suitable for field use.