1. The internal DC power supply is an operating power supply for short-term work, with a small capacity. Do not exceed the parameters in the manual.
2. Before connecting the break contact wires, the ground wire must be connected first, so that the internal anti-induction high voltage circuit is put into operation to avoid damaging the instrument's break channel.
3. The external synchronization of the instrument is a live synchronization method, and the external synchronization line is shared with the internal synchronization open/close control line.
4. When using internal or external synchronization, be sure to make the corresponding selection in the instrument menu to avoid the instrument not receiving the synchronization signal.
Environmental group: belongs to Group III instruments in GB6587.1-1986 "General Outline of Environmental Testing for Electronic Measuring Instruments".
lType: Portable
lPackaging: Aluminum alloy case
lWorking power supply: AC220V±10%
lFrequency: 50Hz±5%
lAmbient temperature: -10°C~40°C
lRelative humidity: ≤85%
lInsulation resistance: ≤2MΩ
lDielectric strength: The power input line to the casing can withstand a withstand voltage test of 1.5KV for 1 minute.
lTime test range: 1~499.9ms Resolution: 0.01ms Accuracy ≤0.1ms
lSpeed test range: 15m/s Resolution: 0.01m/s Accuracy ±1% reading + 2 digits
lStroke test range: unlimited Resolution: 0.01mm Accuracy ±1% reading + 2 digits
lDC power supply selection range: 25-265V/10A Resolution: 1V: Accuracy ≤±1%
Input power: 220V±10% 50Hz±10% Atmospheric pressure: 86~106kpa Temperature: -10~40℃ Humidity: ≦80%RH